Those aren’t supposed to be round on top.

  • Sir_Kevin@lemmy.dbzer0.com
    link
    fedilink
    English
    arrow-up
    17
    ·
    1 day ago

    At last it’s an inexpensive and easy fix. Just buy another capacitor with the same specs and swap them out. Better yet, buy two! Keep one as a backup.

    • Canonical_Warlock@lemmy.dbzer0.com
      link
      fedilink
      English
      arrow-up
      1
      ·
      8 hours ago

      If there are other start components then those should also be swapped. One component failing can weaken the others, especially the start relay.

    • Trihilis@ani.social
      link
      fedilink
      English
      arrow-up
      13
      ·
      1 day ago

      Don’t buy an electrolytic capacitor as back up and store then over a long time. They will degrade and will be bad when you finally need them.

      MKP/MKT capacitors are an exception since they don’t degrade the same.

      • Canonical_Warlock@lemmy.dbzer0.com
        link
        fedilink
        English
        arrow-up
        1
        ·
        8 hours ago

        Eh, they do age but a spare capacitor sitting in a likely climate controlled building and not being used isn’t going to age nearly as quickly as the one in use likely in the outdoors. Will it be as good as a brand new one? No. But it will be damn near as good and it will be on hand when you need it.

        At the same time though, if a motor kills start components often enough that you need to keep a spare on hand then there is something wrong with that motor or your power source.

    • rumba@lemmy.zipOP
      link
      fedilink
      English
      arrow-up
      8
      ·
      1 day ago

      Yeah, I bought one to make sure that was the only problem. It just came back up so, now I’ll pull the furnace apart and find what size it uses for the blower keep them both on hand.

      • Madison420@lemmy.world
        link
        fedilink
        English
        arrow-up
        5
        ·
        22 hours ago

        They can blow on their own but chances are you have a junk contactor or a fan that draws too much amperage.

        • Sir_Kevin@lemmy.dbzer0.com
          link
          fedilink
          English
          arrow-up
          3
          ·
          21 hours ago

          It’s also possible a critter shorted the contacts. Happens all the time in Florida. Usually the fried lizard is still there.

          • Madison420@lemmy.world
            link
            fedilink
            English
            arrow-up
            5
            ·
            20 hours ago

            Then it certainly shouldn’t have failed yet so either high cycle rate or high draw.

            Clean both coils and keep watch on how often it runs and how long it stays running for a couple weeks. Also if you still have a analog bimetallic thermostat those can fail and cause rapid cycling and if the compressor isn’t smart enough to delay they can cycle themselves to death.

            • rumba@lemmy.zipOP
              link
              fedilink
              English
              arrow-up
              3
              ·
              16 hours ago

              keep watch on how often it runs and how long it stays running for a couple weeks. Also if you still have a analog bimetallic thermostat those can

              It’s on an ecobee which appears to be behaving, pulling data from homeassistant on emporia power, it seems to be pretty chill.

              she’s 1.5 ton pulling 1300 watts while running which actually seems low to me.